The three extended end-plate moment connections in Figure 6.1 are prequalified for use in IMF and SMF systems, except in SMF systems where the column is in direct contact with concrete structural slabs. The exception applies only when steel headed stud anchors are used to attach the concrete slab to the connected beam and is because of the lack of test data. Prequalification testing has generally been performed with bare steel specimens. Sumner and Murray (2002) performed one test in which a slab was present. In this test, headed stud anchors were installed from near the end-plate moment connection to the end of the beam, and the concrete was in contact with the column flanges and web. The lower bolts failed prematurely by tension rupture because of the increase in the distance from the neutral axis due to the presence of the composite slab. In later testing, Murray repeated this test but placed a flexible material between the vertical face of the end plate and the slab to inhibit slab participation in transfer of load to the column. This specimen performed acceptably and resulted in provisions for using concrete structural slabs when such flexible material is placed between the slab and the end plate.