H6.1 Scope
Composite plate shear walls—concrete encased (C-PSW/CE) shall be designed in accordance with this section. This section is applicable to C-PSW/CE consisting of steel plates with reinforced concrete encasement on one or both sides of the plate and structural steel sections or composite boundary members.
H6.2 Basis of Design
C-PSW/CE designed in accordance with these provisions are expected to provide significant inelastic deformation capacity through yielding in the plate webs. The horizontal boundary elements (HBE) and vertical boundary elements (VBE) adjacent to the composite webs shall be designed to remain essentially elastic under the maximum forces that can be generated by the fully yielded steel webs along with the reinforced concrete webs after the steel web has fully yielded, except that plastic hinging at the ends of HBE is permitted.
H6.3 Analysis
H6.3a Webs
The analysis shall account for openings in the web.
H6.3b Other Members and Connections
Columns, beams, and connections in C-PSW/CE shall be designed to resist seismic forces determined from an analysis that includes the expected strength of the steel webs in shear, 0.6RyFyAsp, and any reinforced concrete portions of the wall active at the design earthquake displacement,
where
horizontal area of the stiffened steel plate, in.
specified minimum yield stress, ksi (MPa)
ratio of the expected yield stress to the specified minimum yield stress,
The VBE are permitted to yield at the base.
H6.4 System Requirements
H6.4a Steel Plate Thickness
Steel plates with thickness less than 3/8 in. (10 mm) are not permitted.
H6.4b Stiffness of VBE
The VBE shall satisfy the requirements of Section F5.4a.
H6.4c HBE-to-VBE Connection Moment Ratio
The beam-column moment ratio shall satisfy the requirements of Section F5.4b.
H6.4d Bracing
HBE shall be braced to satisfy the requirements for moderately ductile members.
H6.4e Openings in Webs
Boundary members shall be provided around openings in shear wall webs as required by analysis.
H6.5 Members
H6.5a Basic Requirements
Steel and composite HBE and VBE shall satisfy the requirements of Section D1.1 for highly ductile members.
H6.5b Webs
The design shear strength, , for the limit state of shear yielding with a composite plate conforming to Section H6.5c, shall be determined as follows:
(H6-1)
where
specified minimum yield stress of the plate, ksi (MPa)
The design shear strength of C-PSW/CE with a plate that does not meet the stiffening requirements in Section H6.5c shall be based upon the strength of the plate determined in accordance with Section F5.5 and shall satisfy the requirements of Specification Section G2.
H6.5c Concrete Stiffening Elements
The steel plate shall be stiffened by encasement or attachment to a reinforced concrete panel. Conformance to this requirement shall be demonstrated with an elastic plate buckling analysis showing that the composite wall is able to resist a nominal shear force equal to , as determined in Section H6.5b.
The concrete thickness shall be a minimum of 4 in. (100 mm) on each side when concrete is provided on both sides of the steel plate and 8 in. (200 mm) when concrete is provided on one side of the steel plate. Steel headed stud anchors or other mechanical connectors shall be provided to prevent local buckling and separation of the plate and reinforced concrete. Longitudinal and transverse reinforcement shall be provided in the concrete encasement to meet or exceed the requirements in ACI 318, Sections 11.6 and 11.7. The reinforcement ratio in both directions shall not be less than 0.0025. The maximum spacing between bars shall not exceed 18 in. (450 mm).
H6.5d Boundary Members
Structural steel sections and composite boundary members shall be designed to resist the expected shear strength of steel plate and any reinforced concrete portions of the wall active at the design earthquake displacement. Composite and reinforced concrete boundary members shall also satisfy the requirements of Section H5.5b. Structural steel boundary members shall also satisfy the requirements of Section F5.
H6.5e Protected Zones
There are no designated protected zones.
H6.6 Connections
H6.6a Demand Critical Welds
The following welds are demand critical welds and shall satisfy the requirements of Sections A3.4b and I2.3:
- (a) Groove welds at column splices
- (b) Welds at the column-to-base plate connections
Exception: Welds need not be considered demand critical when both of the fol- lowing conditions are met.
- (1) Column hinging at, or near, the base plate is precluded by conditions of restraint.
- (2) There is no net tension under load combinations including the overstrength seismic load.
- (c) Welds at HBE-to-VBE connections
H6.6b HBE-to-VBE Connections
HBE-to-VBE connections shall satisfy the requirements of Section F5.6b.
H6.6c Connections of Steel Plate to Boundary Elements
The steel plate shall be continuously welded or bolted on all edges to the structural steel framing and/or steel boundary members, or the steel component of the composite boundary members. Welds and/or slip-critical high-strength bolts required to develop the nominal shear strength of the plate shall be provided.
H6.6d Connections of Steel Plate to Reinforced Concrete Panel
The steel anchors between the steel plate and the reinforced concrete panel shall be designed to prevent its overall buckling. Steel anchors shall be designed to satisfy the following conditions.
H6.6d.1 Tension in the Connector
The steel anchor shall be designed to resist the tension force resulting from inelastic local buckling of the steel plate.
H6.6d.2 Shear in the Connector
The steel anchors collectively shall be designed to transfer the expected strength in shear of the steel plate or reinforced concrete panel, whichever is smaller.
H6.6e Column Splices
In addition to the requirements of Section D2.5, column splices shall comply with the requirements of this section. Where welds are used to make the splice, they shall be complete-joint-penetration groove welds. When column splices are not made with groove welds, they shall have a required flexural strength that is at least equal to the plastic moment, , of the smaller composite column. The required shear strength of column web splices shall be at least equal to , where is the sum of the plastic moments at the top and bottom ends of the composite column and is the height of the story. For composite columns, the plastic flexural strength shall satisfy the requirements of Specification Chapter I with consideration of the required axial strength, .