Where the required strength defined in these Provisions refers to the capacity-limited seismic load, the capacity-limited horizontal seismic load effect, , shall be determined in accordance with these Provisions, substituted for the horizontal seismic load effect including overstrength, , and applied as prescribed by the load combinations in the applicable building code.
Where the required strength defined in these Provisions refers to the overstrength seismic load, shall be determined using the overstrength factor, , and applied as prescribed by the load combinations in the applicable building code. Where the required strength refers to the overstrength seismic load, it is permitted to use the capacity-limited seismic load instead.
User Note: The seismic load effect including overstrength is defined in ASCE/ SEI 7, Section 12.4.3. In ASCE/SEI 7, Section 12.4.3.1, is determined using Equation 12.4-7: need not be taken larger than . Therefore, where these Provisions refer to capacity-limited seismic load, it is intended that replace as specified in ASCE/SEI 7, Section 12.4.3.2, and use of ASCE/ SEI 7, Equation 12.4-7, is not permitted. However, where these Provisions refer to the overstrength seismic load, is permitted to be taken as calculated in ASCE/ SEI 7, Equation 12.4-7, with a maximum value of equal to .