IS 800:2007, General Construction in Steel — Code of Practice
Last Updated 29 Oct 2026
Hover any section to copy its link or text, ask Copilot about it, or bookmark it.
The fundamental natural frequency can be estimated by assuming full composite action, even in non-composite construction. This frequency, f1 for a simply supported one way system is given by
fi=156EIT/WL4
where
E= modulus of elasticity of steel, MPa
lT= transformed moment of inertia of the one way system (in terms of equivalent steel) assuming the concrete flange of width equal to the spacing of the beam to be effective, in mm4;
L= span length, in mm; and
W= dead load of the one way joist, in N/mm
If the one way joist system is supported by a flexible beam running perpendicular with the natural frequency f2, the floor frequency may be reduced to fr, given by:
Sl No. (1)
System (2)
Critical Damping Percent (3)
i)
Fully composite construction
2
ii)
Bare steel beam and concrete deck
3-4
iii)
Floor with finishes, false ceiling, fire proofing, ducts furniture
6
iv)
Partitions not located along a support or not spaced farther apart than 6 m and partitions oriented in orthogonal directions