Members subject to a three-sided fire exposure condition shall be considered in separate groups unless the following conditions are satisfied:
- a) The characteristics of the members of a group as given below, shall not vary from one another by more than
- Concrete density: , and
- Effective thickness (h_e): \frac{largest in group}{smallest in group} \leq 1.25.
where the effective thickness is equal to the cross-sectional area excluding voids per unit width, as shown in Fig. 25A.
- b) Rib voids shall either be:
- all open; or
- all blocked as shown in Fig. 25B.
- c) Concrete slabs may incorporate permanent steel deck formwork.