5.1 Cement
The cement used shall be any of the following and the type selected should be appropriate for the intended use:
- a) 33 Grade ordinary Portland cement conforming to IS 269
- b) 43 Grade ordinary Portland cement conforming to IS 8112
- c) 53 Grade ordinary Portland cement conforming to IS 12269
- d) Rapid hardening Portland cement conforming to IS 8041
- e) Portland slag cement conforming to IS 455
- f) Portland pozzolana cement (fly ash based) conforming to IS 1489 (Part 1)
- g) Portland pozzolana cement (calcined clay based) conforming to IS 1489 (Part 2)
- h) Hydrophobic cement conforming to IS 8043
- j) Low heat Portland cement conforming to IS 12600
- k) Sulphate resisting Portland cement conforming to IS 12330
Other combinations of Portland cement with mineral admixtures (see 5.2) of quality conforming with relevant Indian Standards laid down may also be used in the manufacture of concrete provided that there are satisfactory data on their suitability, such as performance test on concrete containing them.
5.1.1
Low heat Portland cement conforming to IS 12600 shall be used with adequate precautions with regard to removal of formwork, etc.
5.1.2
High alumina cement conforming to IS 6452 or supersulphated cement conforming to IS 6909 may be used only under special circumstances with the prior approval of the engineer-in-charge. Specialist literature may be consulted for guidance regarding the use of these types of cements.
5.1.3
The attention of the engineers-in-charge and users of cement is drawn to the fact that quality of various cements mentioned in 5.1 is to be determined on the basis of its conformity to the performance characteristics given in the respective Indian Standard Specification for that cement. Any trade-mark or any trade name indicating any special features not covered in the standard or any qualification or other special performance characteristics sometimes claimed/ indicated on the bags or containers or in advertisements alongside the 'Statutory Quality Marking' or otherwise
have no relation whatsoever with the characteristics guaranteed by the Quality Marking as relevant to that cement. Consumers are, therefore, advised to go by the characteristics as given in the corresponding Indian Standard Specification or seek specialist advise to avoid any problem in concrete making and construction.
5.2 Mineral Admixtures
5.2.1 Pozzolanas
Pozzolanic materials conforming to relevant Indian Standards may be used with the permission of the engineer-in-charge, provided uniform blending with cement is ensured.
5.2.1.1 Fly ash (pulverized fuel ash)
Fly ash conforming to Grade 1 of IS 3812 may be used as part replacement of ordinary Portland cement provided uniform blending with cement is ensured.
5.2.1.2 Silica fume
Silica fume conforming to a standard approved by the deciding authority may be used as part replacement of cement provided uniform blending with the cement is ensured.
NOTE—The silica fume (very fine non-crystalline silicon dioxide) is a by-product of the manufacture of silicon, ferrosilicon or the like, from quartz and carbon in electric arc furnace. It is usually used in proportion of 5 to 10 percent of the cement content of a mix.
5.2.1.3 Rice husk ash
Rice husk ash giving required performance and uniformity characteristics may be used with the approval of the deciding authority.
NOTE—Rice husk ash is produced by burning rice husk and contain large proportion of silica. To achieve amorphous state, rice husk may be burnt at controlled temperature. It is necessary to evaluate the product from a particular source for performance and uniformity since it can range from being as deleterious as silt when incorporated in concrete. Water demand and drying shrinkage should be studied before using rice husk.
5.2.1.4 Metakaoline
Metakaoline having fineness between 700 to 900 m²/kg may be used as pozzolanic material in concrete.
NOTE-Metakaoline is obtained by calcination of pure or refined kaolintic clay at a temperature between 650°C and 850°C, followed by grinding to achieve a fineness of 700 to 900 m³/kg. The resulting material has high pozzolanicity.
5.2.2 Ground Granulated Blast Furnace Slag
Ground granulated blast furnace slag obtained by grinding granulated blast furnace slag conforming to IS 12089 may be used as part replacement of ordinary
Portland cements provided uniform blending with cement is ensured.
5.3 Aggregates
Aggregates shall comply with the requirements of IS 383. As far as possible preference shall be given to natural aggregates.
5.3.1
Other types of aggregates such as slag and crushed overburnt brick or tile, which may be found suitable with regard to strength, durability of concrete and freedom from harmful effects may be used for plain concrete members, but such aggregates should not contain more than 0.5 percent of sulphates as SO₃ and should not absorb more than 10 percent of their own mass of water.
5.3.2
Heavy weight aggregates or light weight aggregates such as bloated clay aggregates and sintered fly ash aggregates may also be used provided the engineer-in-charge is satisfied with the data on the properties of concrete made with them.
NOTE—Some of the provisions of the code would require modification when these aggregates are used; specialist literature may be consulted for guidance.
5.3.3 Size of Aggregate
The nominal maximum size of coarse aggregate should be as large as possible within the limits specified but in no case greater than one-fourth of the minimum thickness of the member, provided that the concrete can be placed without difficulty so as to surround all reinforcement thoroughly and fill the corners of the form. For most work, 20 mm aggregate is suitable. Where there is no restriction to the flow of concrete into sections, 40 mm or larger size may be permitted. In concrete elements with thin sections, closely spaced reinforcement or small cover, consideration should be given to the use of 10 mm nominal maximum size.
Plums above 160 mm and up to any reasonable size may be used in plain concrete work up to a maximum limit of 20 percent by volume of concrete when specifically permitted by the engineer-in-charge. The plums shall be distributed evenly and shall be not closer than 150 mm from the surface.
5.3.3.1
For heavily reinforced concrete members as in the case of ribs of main beams, the nominal maximum size of the aggregate should usually be restricted to 5 mm less than the minimum clear distance between the main bars or 5 mm less than the minimum cover to the reinforcement whichever is smaller.
5.3.4
Coarse and fine aggregate shall be batched separately. All-in-aggregate may be used only where specifically permitted by the engineer-in-charge.
5.4 Water
Water used for mixing and curing shall be clean and
free from injurious amounts of oils, acids, alkalis, salts, sugar, organic materials or other substances that may be deleterious to concrete or steel.
Potable water is generally considered satisfactory for mixing concrete. As a guide the following concentrations represent the maximum permissible values:
- a) To neutralize 100 ml sample of water, usir.g phenolphthalein as an indicator, it should not require more than 5 ml of 0.02 normal NaOH. The details of test are given in 8.1 of IS 3025 (Part 22).
- b) To neutralize 100 ml sample of water, using mixed indicator, it should not require more than 25 ml of 0.02 normal H₂SO₄. The details of test shall be as given in 8 of IS 3025 (Part 23).
- c) Permissible limits for solids shall be as given in Table 1.
5.4.1
In case of doubt regarding development of strength, the suitability of water for making concrete shall be ascertained by the compressive strength and initial setting time tests specified in 5.4.1.2 and 5.4.1.3.
5.4.1.1
The sample of water taken for testing shall represent the water proposed to be used for concreting, due account being paid to seasonal variation. The sample shall not receive any treatment before testing other than that envisaged in the regular supply of water proposed for use in concrete. The sample shall be stored in a clean container previously rinsed out with similar water.
5.4.1.2
Average 28 days compressive strength of at least three 150 mm concrete cubes prepared with water proposed to be used shall not be less than 90 percent of the average of strength of three similar concrete cubes prepared with distilled water. The cubes shall be prepared, cured and tested in accordance with the requirements of IS 516.
5.4.1.3
The initial setting time of test block made with the appropriate cement and the water proposed to be used shall not be less than 30 min and shall not differ by ± 30 min from the initial setting time of control test block prepared with the same cement and distilled water. The test blocks shall be prepared and tested in accordance with the requirements of IS 4031 (Part 5).
5.4.2
The pH value of water shall be not less than 6.
5.4.3 Sea Water
Mixing or curing of concrete with sea water is not recommended because of presence of harmful salts in sea water. Under unavoidable circumstances sea water may be used for mixing or curing in plain concrete with no embedded steel after having given due consideration to possible disadvantages and precautions including use of appropriate cement system.
Table 1 Permissible Limit for Solids
(Clause 5.4)
| SI No. | Tested as per | Permissible Limit, Max | |
|---|---|---|---|
| i) | Organic | IS 3025 (Part 18) | 200 mg/l |
| ii) | Inorganic | IS 3025 (Part 18) | 3 000 mg/l |
| iii) | Sulphates (as SO₂) | IS 3025 (Part 24) | 400 mg/l |
| iv) | Chlorides (as Cl) | IS 3025 (Part 32) | 2 000 mg/l for concrete not containing embedded steel and 500 mg/l for reinforced concrete work |
| v) | Suspended matter | IS 3025 (Part 17) | 2 000 mg/l |
5.4.4
Water found satisfactory for mixing is also suitable for curing concrete. However, water used for curing should not produce any objectionable stain or unsightly deposit on the concrete surface. The presence of tannic acid or iron compounds is objectionable.
5.5 Admixtures
5.5.1
Admixture, if used shall comply with IS 9103. Previous experience with and data on such materials should be considered in relation to the likely standards of supervision and workmanship to the work being specified.
5.5.2
Admixtures should not impair durability of concrete nor combine with the constituent to form harmful compounds nor increase the risk of corrosion of reinforcement.
5.5.3
The workability, compressive strength and the slump loss of concrete with and without the use of admixtures shall be established during the trial mixes before use of admixtures
5.5.4
The relative density of liquid admixtures shall be checked for each drum containing admixtures and compared with the specified value before acceptance.
5.5.5
The chloride content of admixtures shall be independently tested for each batch before acceptance.
5.5.6
If two or more admixtures are used simultaneously in the same concrete mix, data should be obtained to assess their interaction and to ensure their compatibility.
5.6 Reinforcement
The reinforcement shall be any of the following:
- a) Mild steel and medium tensile steel bars conforming to IS 432 (Part 1).
- b) High strength deformed steel bars conforming to IS 1786.
- c) Hard-drawn steel wire fabric conforming to IS 1566.
- d) Structural steel conforming to Grade A of IS 2062.
5.6.1
All reinforcement shall be free from loose mill scales, loose rust and coats of paints, oil, mud or any other substances which may destroy or reduce bond. Sand blasting or other treatment is recommended to clean reinforcement.
5.6.2
Special precautions like coating of reinforcement may be required for reinforced concrete elements in exceptional cases and for rehabilitation of structures. Specialist literature may be referred to in such cases.
5.6.3
The modulus of elasticity of steel shall be taken as 200 kN/mm². The characteristic yield strength of different steel shall be assumed as the minimum yield stress/0.2 percent proof stress specified in the relevant Indian Standard.
5.7 Storage of Materials
Storage of materials shall be as described in IS 4082.